 产品阵容
 型号说明:DCR 030 DC 24V DC 56V
 资料下载:


  • High DC heating performance
  • Integrated thermostat or hygrostat (optional)
  • Small hysteresis
  • Integrated switch module
  • Screw fixing
  • Optical indicator (LED)

The compact high performance fan heater prevents formation of condensation and frost and provides an evenly distributed interior air temperature in enclosures with electric/electronic components. The fan heater is available with an integrated electronic thermostat or integrated electronic hygrostat. The model with thermostat is available with internal or external sensor. The fan heater with integrated hygrostat is equipped with an external sensor. The external sensor can be positioned freely anywhere in the enclosure for precise measurements of temperature and humidity. The DCR 030 was designed as a stationary unit for the bottom of the enclosure. For wall fixing the fan heater DCR 130 is recommended. 

TECHNICAL DATA

Heating element high performance cartridge
Temperature safety cut-out with automatic reset and second-tier one shot fuse
to protect against overheating in case of fan failure
Heater body extruded aluminium profile
Axial fan, ball bearing airflow 160 m³/h, free flow
service life 50,000h at +25 °C (+77 °F)
Connection

2-pole „Push-In“ connection clamp stranded wire1 1.5 mm²
(AWG 16) with strand relief; max. 2.5 mm² (AWG 12)

Casing plastic according to UL94 V-0, black
Mounting screw fixing (M5), torque 2 Nm max., washers have to be used
Fitting position vertical airflow (air outlet up)
Dimensions 166 x 145 x 100 mm
Weight approx. 1.3 kg
Operating temperature -20 to +75 °C (-4 to +167 °F)
Storage temperature -40 to +80 °C (-40 to +176 °F)
Operating/Storage humidity max. 90 % RH (non-condensing)
Protection type/Protection class IP20 / II (double insulated)
Approvals UL File No. E234324, VDE, EAC
Note other versions (heating capacities, setting ranges) as well as operating voltage DC 48 V on request

¹ When connecting with stranded wires, wire end ferrules must be used.

Art. No. Model Operating voltage Heating capacity Recommended
pre-fuse T (time-delay)
Setting range³ temperature / humidity
03092.1-12 Thermostat with
internal sensor
DC 24 V 200 W 25.0 A -20 to +40 °C
03092.1-13 Thermostat with connector
for external sensor²
DC 24 V 200 W 25.0 A -20 to +40 °C
03097.3-12 Thermostat with
internal sensor
DC 56 V 800 W 25.0 A -20 to +40 °C
03097.3-13 Thermostat with connector
for external sensor²
DC 56 V 800 W 25.0 A -20 to +40 °C
03092.1-03 Hygrostat with connector
for external sensor²
DC 24 V 200 W 25.0 A 40 to 90 % RH
03095.3-03 Hygrostat with connector
for external sensor²
DC 56 V 600 W 25.0 A 40 to 90 % RH

² The external sensor needs to be ordered separately.
³ Switch difference temperature: 3 K (±1 K tolerance) at +25 °C (+77 °F), 50 % RH; switch difference humidity: 4 % RH (±1 % tolerance) at +25 °C (+77 °F), 50 % RH.

ACCESSORIES

The external sensor is not included in the delivery of the DCR 030. It can be ordered separately.

EXTERNAL SENSOR

The external sensor can be positioned freely anywhere in the enclosure for precise measurements of temperature and humidity. 

Art. No. Length
267071 1 m
267072 2 m
267126 3 m

 

TECHNICAL DRAWING

High-performance Fan Heater DCR 030

 Copyright © 2009 深圳市杰诚伟业科技发展有限公司 备案序号:粤ICP备161105340号